Heat recovery ventilators and energy recovery ventilators — Testing and calculating methods for seasonal performance factor — Part 1: Sensible heating recovery seasonal performance factors of heat recovery ventilators (HRV)

This document specifies the testing and calculating methods for sensible heating recovery seasonal performance factor of heat recovery ventilators (HRV) covered by ISO 16494-1. This document also specifies the test conditions and the corresponding test procedures for determining the sensible heating recovery seasonal performance factor of HRV and is intended for use only in marking, comparison, and certification purposes. For the purposes of this document, the rating conditions are those specified in ISO 16494-1 and in Annex B. The procedures of this document may be used for other temperature conditions.

Ventilateurs récupérateurs de chaleur et ventilateurs récupérateurs d'énergie — Méthodes d'essai et de calcul des facteurs de performances saisonnières — Partie 1: Facteurs de performances saisonnières de la récupération de chaleur sensible des ventilateurs récupérateurs de chaleur (HRV)

General Information

Status
Published
Publication Date
28-Aug-2023
Current Stage
6060 - International Standard published
Start Date
29-Aug-2023
Due Date
11-Sep-2023
Completion Date
29-Aug-2023
Ref Project

Buy Standard

Standard
ISO 5222-1:2023 - Heat recovery ventilators and energy recovery ventilators — Testing and calculating methods for seasonal performance factor — Part 1: Sensible heating recovery seasonal performance factors of heat recovery ventilators (HRV) Released:29. 08. 2023
English language
22 pages
sale 15% off
Preview
sale 15% off
Preview
Draft
ISO/FDIS 5222-1 - Heat recovery ventilators and energy recovery ventilators — Testing and calculating methods for seasonal performance factor — Part 1: Sensible heating recovery seasonal performance factors of HRV Released:2/25/2022
English language
27 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

INTERNATIONAL ISO
STANDARD 5222-1
First edition
2023-08
Heat recovery ventilators and energy
recovery ventilators — Testing and
calculating methods for seasonal
performance factor —
Part 1:
Sensible heating recovery seasonal
performance factors of heat recovery
ventilators (HRV)
Ventilateurs récupérateurs de chaleur et ventilateurs récupérateurs
d'énergie — Méthodes d'essai et de calcul des facteurs de
performances saisonnières —
Partie 1: Facteurs de performances saisonnières de la récupération de
chaleur sensible des ventilateurs récupérateurs de chaleur (HRV)
Reference number
ISO 5222-1:2023(E)
© ISO 2023

---------------------- Page: 1 ----------------------
ISO 5222-1:2023(E)
COPYRIGHT PROTECTED DOCUMENT
© ISO 2023
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
  © ISO 2023 – All rights reserved

---------------------- Page: 2 ----------------------
ISO 5222-1:2023(E)
Contents Page
Foreword .iv
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Symbols and abbreviated terms.2
5 Tests . 3
5.1 General requirements . 3
5.2 Test conditions . 3
5.3 Test methods . 3
5.3.1 General . 3
5.3.2 Energy saving stage limit temperature . 4
5.3.3 Sensible heating recovery performance test . . 4
5.3.4 Determination of bypass outdoor temperature . 4
5.3.5 Measurement of power input of heat recovery ventilator with bypass
ventilation function . 4
5.3.6 Determination of the frosting temperature by test . 5
6 Calculations . 6
6.1 Gross sensible heating recovery effectiveness (ε ) . 6
sh
6.2 Sensible heating coefficient of energy . 6
6.2.1 Sensible heating coefficient of energy: ducted ventilators . 6
6.2.2 Sensible heating coefficient of energy: unducted ventilators . 7
6.3 Calculation of seasonal performance factor of sensible heating recovery (F ) . 7
sh
6.3.1 Reference outdoor air heating load and sensible heating recovery capacity . 7
6.3.2 The characteristics of sensible heating recovery capacity against outdoor
temperature . 8
6.3.3 Power input characteristics of sensible heating recovery against outdoor
temperature . 9
6.3.4 Outdoor temperature bin distribution for heating . 10
6.3.5 Calculation of seasonal sensible heating recovery capacity (E ) . 10
sh
6.3.6 Calculation of seasonal sensible heating recovery power input (P ) . 10
in,E
6.3.7 Calculation of seasonal performance factor for sensible heating recovery
(F ) . 11
sh
7 Test report .11
Annex A (informative) The schematic diagram of HRV heating (H) operation .12
Annex B (informative) The default outdoor temperature bin distribution for heating .14
Annex C (normative) Method of determination of the temperature T .15
F,0
Annex D (informative) Calculating method for seasonal performance factor when setting a
specific application heating load .16
Annex E (normative) Calculation of the bypass outdoor temperature .18
Annex F (informative) Report template .19
Bibliography .22
iii
© ISO 2023 – All rights reserved

---------------------- Page: 3 ----------------------
ISO 5222-1:2023(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO's adherence to
the World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT), see
www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 86, Refrigeration and air-conditioning,
Subcommittee SC 6, Testing and rating of air-conditioners and heat pumps.
A list of all parts in the ISO 5222 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
iv
  © ISO 2023 – All rights reserved

---------------------- Page: 4 ----------------------
INTERNATIONAL STANDARD ISO 5222-1:2023(E)
Heat recovery ventilators and energy recovery
ventilators — Testing and calculating methods for seasonal
performance factor —
Part 1:
Sensible heating recovery seasonal performance factors of
heat recovery ventilators (HRV)
1 Scope
This document specifies the testing and calculating methods for sensible heating recovery seasonal
performance factor of heat recovery ventilators (HRV) covered by ISO 16494-1.
This document also specifies the test conditions and the corresponding test procedures for determining
the sensible heating recovery seasonal performance factor of HRV and is intended for use only in
marking, comparison, and certification purposes. For the purposes of this document, the rating
conditions are those specified in ISO 16494-1 and in Annex B. The procedures of this document may be
used for other temperature conditions.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
ISO 16494-1:2022, Heat recovery ventilators and energy recovery ventilators — Method of test for
performance — Part 1: Development of metrics for evaluation of energy related performance
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 16494-1 and the following
apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1
heat recovery
transfer of sensible energy from exhaust air to supply air in the HRV while heating
3.2
bypass ventilation function
function for reducing power input of the fans while the heat energy recovered is less than the additional
energy input due to overcoming the resistance of recovery heat exchanger during its operation time
Note 1 to entry: The bypass function makes the supply air and exhaust air go through the heat recovery exchanger
bypass with energy saving control.
1
© ISO 2023 – All rights reserved

---------------------- Page: 5 ----------------------
ISO 5222-1:2023(E)
3.3
coefficient of energy
total sensible heating energy exchanged between the air streams plus the power
value of moving air, divided by the power input
Note 1 to entry: The formula for determining C is given in 6.2.1 and C in 6.2.2.
sh,d,t,j sh,u,d,t,j
3.4
gross effectiveness
measured effectiveness, not adjusted for leakage, motor heat gain, or heat transfer
through the unit casing
Note 1 to entry: The sensible heating gross effectiveness of an HRV, at equal airflow, is described in
ISO 16494-1:2022, 9.5.
3.5
bypass outdoor temperature
T
b
outdoor temperature in heating conditions, at which the electric power reduction to the HRV by
operating in bypass mode is equal to the saving of electric power input to the heating system due to the
heat recovered by the HRV
3.6
seasonal performance factor of sensible heating recovery
F
sh
ratio of seasonal amount of sensible heat recovered together with power value of moving air to the
whole electricity input of HRV, under the rating conditions and seasonal outdoor temperature bins
selected from this standard
3.7
building heating balance temperature
T
BHB
outdoor air temperature at which building internal heat gain, solar radiation, and so on, equals to heat
loss through the building envelope
4 Symbols and abbreviated terms
Symbol Description Unit
E Capacity of seasonal sensible heating recovery Wh
sh
C Sensible heating coefficient of energy for ducted ventilator at outdoor air W/W
sh,d,t,j
bin temperature t
j
C Sensible heating coefficient of energy for unducted ventilator at outdoor W/W
sh,u,d,t,j
air bin temperature t
j
c Specific heat of leaving supply air (SA) kJ/kg· °C
p
L Reference outdoor air sensible heating load at outdoor air bin temperature t W
sh,t,j j
n Bin hours which the outdoor air bin temperature occurs h
j
n Number of temperature bins -
P Power input to ventilator at outdoor air bin temperature t W
in,t,j j
P Power input to the HRV to operate the fans at outdoor air bin temperature W
in,no,t,j
t for all stages, for HRVs without bypass
j
P Power input to the HRV at outdoor air bin temperature t for bin temper- W
in,by,t,j j
ature in stage 1 or 2, for HRVs with bypass
P Power input to a supplementary preheater at full capacity W
in,h,t,j
P Ventilation power input of the HRV at outdoor air bin temperature W
in,v,t,j
P Power value of moving air at outdoor air bin temperature t J/s or W
vma,t,j j
2
  © ISO 2023 – All rights reserved

---------------------- Page: 6 ----------------------
ISO 5222-1:2023(E)
Symbol Description Unit
P Electricity power input of seasonal sensible heating recovery Wh
in,E
Q Net supply mass flow rate kg/s
m2, net
F Seasonal performance factor of sensible heating recovery Wh/Wh
sh
T Outdoor air temperature when HRV operates under air bypass function °C
b
T The outdoor air bin temperature at which the frost occurs °C
F
T Temperature defined in ISO 16494-1:2022, Table 2 as T5/T6/T7 °C
set,h
ε Gross sensible heating effectiveness of HRV %
sh
ϕ Sensible heat recovery capacity of the HRV at outdoor air bin temperature t W
sh,t,j j
5 Tests
5.1 General requirements
The test conditions used, the accuracy and uncertainties of the instruments used shall conform with
ISO 16494-1 and those in this document.
5.2 Test conditions
For the purpose of ε , E and F , there are three standard test conditions T5/T6/T7 corresponding to
sh sh sh
ISO 16494-1:2022, Table 2. The HRV shall be tested at one of the three test conditions, which shall be
selected to most closely represent the outdoor temperature bin distribution in the region as described
in Annex B and Annex D.
Outdoor temperature bin distribution and bin hours differ from region to region. If bin hours are set to a
certain value for a certain region, the integrated value of heating load and electric energy consumption
can be determined.
Table 1 shows the requirement of default values and the reference outdoor temperature bin distribution
for test and calculation. In case of setting other outdoor temperature bin distribution, refer to the
setting method as described in Annex D.
Table 1 — Conditions of performance test (heating)
Outdoor air temperature Indoor air temperature Application
(°C) (°C) temperature bin type
for calculation
Dry bulb Wet bulb Dry bulb Wet bulb
T5 2 1 21 14 In Annex B or D
T6 5 3 20 15
T7 7 6 20 12
NOTE Allowable variation of readings is given in Table F.2 in ISO 16494-1:2022.
5.3 Test methods
5.3.1 General
For higher seasonal energy performance, HRV can be designed with airflow bypass function integrating
fan speed control or airflow dampers adjust, which can change the fan power input according to
different outdoor temperature condition, while keeping necessary aerodynamic performance.
3
© ISO 2023 – All rights reserved

---------------------- Page: 7 ----------------------
ISO 5222-1:2023(E)
5.3.2 Energy saving stage limit temperature
To assess the energy saving ability of HRV, the operation stages under the application temperature bin
are shown in Annex A using a schematic diagram.
5.3.3 Sensible heating recovery performance test
5.3.3.1 Standard condition performance tests
The sensible heating recovery performance tests shall be conducted in accordance with ISO 16494-1.
The sensible heating recovery performance, efficiency, as well as airflow and static pressure shall be
measured corresponding to the selected standard heating performance tests conditions in Table 1.
5.3.3.2 Determination of performance at application climate
The sensible heating recovery performance under certain climate temperature bins shall also be
determined by calculation using the temperature bins see Annex B and Annex D.
5.3.4 Determination of bypass outdoor temperature
The manufacturer shall specify the value of bypass outdoor temperature. The laboratory shall verify
that the unit under test is functioning and what the test action temperature is. If it is not specified by
the manufacturer, the laboratory shall calculate the outdoor bypass temperature and set it as the T in
b
accordance with Annex E.
5.3.5 Measurement of power input of heat recovery ventilator with bypass ventilation function
5.3.5.1 The manufacturer may provide information on how to set the bypass function if requested by
the testing laboratories.
NOTE 1 Due to the additional air resistance of the heat recovery exchanger, when the heat energy recovered
is less than the additional energy input due to overcoming the resistance of recovery heat exchanger during
its operation time, the equipment can provide the bypass ventilation function to reduce the additional energy
consumption, when only ventilation is necessary.
NOTE 2 When the bypass ventilation function acts, there can be several means to reduce the additional energy
consumption (e.g. with fan speed control or valve control in the fan’s inlet or outlet, etc., to keep the same airflow
rate and pressure as rating performance condition).
5.3.5.2 The tests shall be conducted at the required control set which allows steady state operation of
the equipment at the given test conditions.
5.3.5.3 Test of unit with bypass ventilation function and fan speed control:
a) Set up the bypass ventilation function according to the manufacturer's instructions.
b) Adjust test auxiliary device to keep the average pressure value at air outlet and inlet of unit in
Figure A.1 of ISO 16494-1:2022, within the 5 % of tested unit’s nominal value, the airflow rate
larger or equal to its nominal value.
c) According to ISO 16494-1, measure and record the data of airflow rate, the pressure and electricity
power input.
d) Determine and record the outdoor temperature at which the bypass ventilation function acts,
either by manufacturer's statement, or by measure. The power input value measured when bypass
ventilation functions is activated is recorded as the bypass ventilation function power input, used
for calculation for F corresponding to each outdoor bin temperature in ventilation period.
sh
4
  © ISO 2023 – All rights reserved

---------------------- Page: 8 ----------------------
ISO 5222-1:2023(E)
5.3.5.4 Test of unit with bypass ventilation function and with electric driving air damper
automatically, but without fan speed control:
a) Set up the bypass ventilation function according to the manufacturer's instructions.
b) Adjust the test auxiliary device to keep the average pressure value within the 5 % of the tested
unit’s nominal value, the airflow rate larger or equal to its nominal value.
c) Determine and record the outdoor temperature at which the bypass ventilation function acts,
either by the manufacturer's statement, or by measurement. The power input value measured when
bypass ventilation function is on shall be recorded as the bypass ventilation function power input,
used for the calculation of F corresponding to each outdoor bin temperature in the ventilation
sh
period.
5.3.5.5 Test of equipment with bypass ventilation function and without fan speed control and
without automatic adjust air damper:
a) Set up the bypass ventilation function according to manufacturer’s instruction.
b) According to ISO 16494-1, do not adjust any of the test auxiliary devices during test and record the
data of airflow rate, the pressure and power input.
c) Determine and record the outdoor temperature that the bypass ventilation function acts, either by
the manufacturer's statement, or by test.
d) The power input value measured when bypass ventilation functions on is recorded as the bypass
ventilation function power input, used for calculation for F corresponding to each outdoor bin
sh
temperature in ventilation period.
5.3.5.6 Test of equipment with no bypass ventilation function:
For the equipment with no bypass ventilation function, the power input is the value as same as in 5.3.3.1
all stages, which shall be used for calculation for F corresponding to each outdoor temperature in
sh
ventilation period.
5.3.6 Determination of the frosting temperature by test
5.3.6.1 The frost temperature test shall be conducted in accordance with ISO 16494-1.
The manufacturer may provide information on how to operate the equipment if requested by the
testing laboratories.
5.3.6.2 The test condition shall be as follows:
a) The airflow rate and static pressure shall keep the same as 5.3.3.1.
b) The entering exhaust air (RA) temperature shall be kept at conditions T5/T6/T7 specified in
Table 1 and entering supply air (OA) temperature shall be gradually reduced from 0 °C, or, in order
to reduce the duration time of the test, from the T , which is described in Annex C, plus 2 K.
F,0
NOTE The calculation of T refers to Annex C.
F,0
5.3.6.3 Confirmation of frost outdoor air temperature:
a) Turn off the supplement heat function for anti-frost.
b) Conduct the tests of gross sensible heating recovery effectiveness of HRV by changing outdoor
temperature from the T plus 2 K to lower temperature. While adjusting the outdoor air
F,0
temperature, keep the reducing rate of temperature not less than 0,5 K per hour and not greater
than 1,0 K per hour.
5
© ISO 2023 – All rights reserved

---------------------- Page: 9 ----------------------
ISO 5222-1:2023(E)
c) Record the inlet and outlet air parameters so that gross sensible heating effectiveness can be
calculated every 0,5 h.
d) Calculate the gross sensible heat effectiveness in accordance with ISO 16494-1:2022, 9.5.
e) If the absolute value of the change of the gross sensible heating effectiveness between the outdoor
temperature t and temperature t is greater than 5 %, the higher temperature of the outdoor
j j-1
temperatures is confirmed as a frost outdoor temperature.
f) Compare the tested T with the one in practice, if the tested T is lower than the one in practice,
F F
select the temperature in practice as the stage limitation temperature, otherwise, the tested T
F
shall be the stage limitation temperature.
5.3.6.4 Data collection:
During the frost temperature tests, airflow rate, static pressure, barometer pressure and power input
as well as air temperature shall be collected and recorded. A continuous air temperature variation
curve drawing shall be necessary.
6 Calculations
6.1 Gross sensible heating recovery effectiveness (ε )
sh
The gross sensible heating recovery effectiveness of HRV at rated test condition is described in
ISO 16494-1:2022, 9.5.
6.2 Sensible heating coefficient of energy
6.2.1 Sensible heating coefficient of energy: ducted ventilators
The sensible heating coefficient of energy for a ducted ventilator (C ) shall be calculated by
sh,d,t,j
Formula (1):
Qc×× Tt− ×+ε ×1 000 P
()
m2,netp 0 jvsh ma,t,j
C = (1)
sh,d,t,j
P
in,t,j
where
C is the sensible heating coefficient of energy for a ducted ventilator at outdoor air bin tem-
sh,d,t,j
perature t (W/W);
j
T is the dry temperature of entering exhaust air (RA) under ISO 16494-1 standard testing
0
conditions (T5/T6/T7), (°C);
t is the dry temperature of outdoor air corresponding to application temperature bin j (°C);
j
Q is the net supply mass flow rate (kg/s);
m2,net
c is the specific heat of air (kJ/kg· °C);
p
ε is the gross sensible heating recovery effectiveness of HRV at rated test condition is described
sh
in ISO 16494-1:2022, 9.5 (%);
P is the power value of moving air at outdoor air bin temperature t (J/s);
vma,t,j j
P is the input power to ventilator at outdoor air bin temperature t (W).
in,t,j j
6
  © ISO 2023 – All rights reserved

---------------------- Page: 10 ----------------------
ISO 5222-1:2023(E)
6.2.2 Sensible heating coefficient of energy: unducted ventilators
The sensible heating coefficient of energy for an unducted ventilator (C ) is described by
sh,u,d,t,j
Formula (2)
Qc×−× Tt ××ε 1 000
()
m2,netp 0 jsh
C = (2)
sh,u,d,t,j
P
in,t,j
where
C is the sensible heating coefficient of energy for an unducted ventilator at outdoor air bin
sh,u,d,t,j
temperature t (W/W);
j
T is the dry temperature of entering exhaust air (RA) under ISO 16494-1 standard testing
0
conditions (T5/T6/T7) (°C);
t is the dry temperature of outdoor air corresponding to application temperature bin j (°C);
j
Q is the net supply mass flow rate (kg/s);
m2,net
c is the specific heat of leaving supply air (kJ/kg· °C);
p
ε is the gross sensible heating recovery effectiveness of HRV at rated test condition is described
sh
in ISO 16494-1:2022, 9.5;
P is the input power to ventilator (W).
in,t,j
6.3 Calculation of seasonal performance factor of sensible heating recovery (F )
sh
6.3.1 Reference outdoor air heating load and sensible heating recovery capacity
The reference outdoor air heating load shall be by a set of values and be assumed that they are linearly
changing depending on the change of outdoor temperature, the sensible heat recovery capacity is
assumed also linearly changing, see figure in Annex A. Conditions of reference heating load and
recovery capacity is shown in Table 2.
Table 2 — Reference outdoor air sensible heating load and recovery capacity
T5 T6 T7
Outdoor air Temperature (°C) Climate bins Climate bins Climate bins
T indoor air 21 20 20
0
Temperature (°C)
Outdoor air heating load (W) L L L
sh,T5,t,j sh,T6,t,j sh,T7,t,j
Recovery capacity (W) ϕ ϕ ϕ
sh,T5,t,j sh,T6,t,j sh,T7,t,j
where T is the temperature at which outdoor air heating load assumed zero.
0
The outdoor air sensible heating load L at outdoor temperature t , which is necessary to calculate
sh,t,j j
the seasonal sensible heating heat recovery, shall be determined by Formula (3)
LQ=×cT×−t ×1 000 (3)
sh,t,j m2,netp 0 j
7
© ISO 2023 – All rights reserved

---------------------- Page: 11 ----------------------
ISO 5222-1:2023(E)
where
L is outdoor air sensible heating load at the outdoor temperature t ;
sh,t,j j
Q
is the net supply mass flow rate (kg/s);
m2,net
T is the dry temperature of entering exhaust air (RA) under ISO 16494-1 standard testing
0
conditions (T5/T6/T7) (°C);
t is the dry temperature of outdoor air corresponding to application temperature bin j (°C).
j
6.3.2 The characteristics of sensible heating recovery capacity against outdoor temperature
Sensible heating recovery capacity ϕ (W) of the HRV at outdoor temperature t changes depending
sh,t,j j
on outdoor temperatures, as shown in Figure A.1 in Annex A, and it is determined by Formulae (4) and
(5).
The stages are described in Annex A.
a) H Stage 1 ventilation with or without bypass function
For with or without bypass function, recovery capacity ϕ at outdoor temperature t shall be zero.
sh,t,j j
b) H Stage 2 ventilation with or without bypass function at heat recovery mode
For HRV with bypass function, recovery capacity ϕ at outdoor temperature t shall be zero.
sh,t,j j
For HRV without bypass function, recovery capacity ϕ at outdoor temperature t shall be determined
sh,t,j j
by Formula (4)
φε=×L (4)
sh,t,j sh,t,j sh
where
ϕ is the sensible heat recovery capacity of the HRV at outdoor air bin temperature t ;
sh,t,j
...

DRAFT INTERNATIONAL STANDARD
ISO/DIS 5222-1
ISO/TC 86/SC 6 Secretariat: JISC
Voting begins on: Voting terminates on:
2022-04-21 2022-07-14
Heat recovery ventilators and energy recovery
ventilators — Testing and calculating methods for seasonal
performance factor —
Part 1:
Sensible heating recovery seasonal performance factors of
HRV
Ventilateurs récupérateurs de chaleur et ventilateurs récupérateurs d'énergie — Méthodes d'essai et de
calcul des facteurs de performances saisonnières —
Partie 1: Facteurs de performances saisonnières de la récupération de chaleur sensible des ventilateurs
récupérateurs de chaleur (HRV)
ICS: 23.120
THIS DOCUMENT IS A DRAFT CIRCULATED
FOR COMMENT AND APPROVAL. IT IS
THEREFORE SUBJECT TO CHANGE AND MAY
This document is circulated as received from the committee secretariat.
NOT BE REFERRED TO AS AN INTERNATIONAL
STANDARD UNTIL PUBLISHED AS SUCH.
IN ADDITION TO THEIR EVALUATION AS
BEING ACCEPTABLE FOR INDUSTRIAL,
TECHNOLOGICAL, COMMERCIAL AND
USER PURPOSES, DRAFT INTERNATIONAL
STANDARDS MAY ON OCCASION HAVE TO
BE CONSIDERED IN THE LIGHT OF THEIR
POTENTIAL TO BECOME STANDARDS TO
WHICH REFERENCE MAY BE MADE IN
Reference number
NATIONAL REGULATIONS.
ISO/DIS 5222-1:2022(E)
RECIPIENTS OF THIS DRAFT ARE INVITED
TO SUBMIT, WITH THEIR COMMENTS,
NOTIFICATION OF ANY RELEVANT PATENT
RIGHTS OF WHICH THEY ARE AWARE AND TO
PROVIDE SUPPORTING DOCUMENTATION. © ISO 2022

---------------------- Page: 1 ----------------------
ISO/DIS 5222-1:2022(E)
COPYRIGHT PROTECTED DOCUMENT
© ISO 2022
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
  © ISO 2022 – All rights reserved

---------------------- Page: 2 ----------------------
ISO/DIS 5222-1:2022(E)
Contents Page
Foreword .iv
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Symbols and Abbreviated terms . 3
5 Tests . 4
5.1 General requirements . 4
5.2 Test conditions . 4
5.3 Test methods . 4
6 Calculations . 7
6.1 Gross sensible heating recovery efficiency (ε ) . . 7
SEN_h
6.2 Sensible heating coefficient of energy . 7
6.2.1 Sensible heating coefficient of energy: ducted ventilators . 7
6.2.2 Sensible heating coefficient of energy: unducted ventilators . 7
6.3 Calculation of seasonal performance factor of sensible heating recovery (SPF ) . 8
SEN_h
6.3.1 Reference outdoor air heating load and sensible heating recovery capacity . 8
6.3.2 The characteristics of sensible heating recovery capacity against outdoor
temperature . 8
6.3.3 Power input characteristics of sensible heating recovery against outdoor
temperature . 9
6.3.4 Outdoor temperature bin distribution for heating . 10
6.3.5 Calculation of seasonal sensible heating recovery capacity (C ) . 10
SSEN_h
6.3.6 Calculation of seasonal sensible heating recovery power input (PI ). 10
SSEN_h
6.3.7 Calculation of seasonal performance factor for sensible heating recovery
(SPF ) . 11
SEN_h
7 Test report .11
Annex A (informative) The schematic diagram of HRV operation .12
Annex B (informative) Applicable climate bin hours .14
Annex C (normative) Method of determination of the temperature pre-T .16
FROST
Annex D (informative) Calculating method for seasonal performance factor when setting a
specific application heating load .17
Annex E (Normative) The calculation of bypass outdoor temperature .20
Annex F (informative) Report template .21
Bibliography .28
iii
© ISO 2022 – All rights reserved

---------------------- Page: 3 ----------------------
ISO/DIS 5222-1:2022(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2. (see www.iso.org/directives)
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received.(see www.iso.org/patents)
Any trade name used in this document is information given for the convenience of users of this document
and does not constitute an endorsement. Equivalent products can be used if they can be shown to lead
to the same results.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO's adherence to
the World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT), see
www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 86, Refrigeration and air-conditioning,
Subcommittee SC 6, Testing and rating of air-conditioners and heat pumps.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
The parts of ISO 5222 are given as below:
— Part 1: Sensible heating recovery seasonal performance factors of HRV
— Part 2: Sensible cooling recovery seasonal performance factors of HRV
— Part 3: Annual sensible heating and cooling recovery performance factor of HRV
— Part 4: Total heating recovery seasonal performance factors of ERV
— Part 5: Total cooling recovery seasonal performance factors of ERV
— Part 6: Annual total heating and cooling recovery performance factor of ERV
iv
  © ISO 2022 – All rights reserved

---------------------- Page: 4 ----------------------
DRAFT INTERNATIONAL STANDARD ISO/DIS 5222-1:2022(E)
Heat recovery ventilators and energy recovery
ventilators — Testing and calculating methods for seasonal
performance factor —
Part 1:
Sensible heating recovery seasonal performance factors of
HRV
1 Scope
1.1 ISO 5222-1 specifies the testing and calculating methods for sensible heating recovery seasonal
performance factor of HRV covered by ISO 16494-1.
1.2 ISO 5222-1also specifies the test conditions and the corresponding test procedures for
determining the sensible heating recovery seasonal performance factor of HRV and is intended for use
only in marking, comparison, and certification purposes. For the purposes of ISO 5222-1, the rating
conditions are those specified in the standard ISO 16494 and in the Annex B. The procedures of
ISO 5222-1 may be used for other temperature conditions.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
ISO 16494-1:2014, Heat recovery ventilators and energy recovery ventilators — Method of test for
performance : Part1 : Development of metrics for evaluation of energy related performance
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1
heat recovery, sensible heating
transference of sensible energy from exhaust airflow to outdoor airflow in the HRV while heating
3.2
bypass ventilation function
For reducing power input of the fans when the heat recovery profit is less than the additional energy
input due to overcoming the resistance of recovery heat exchangers during its operation time, the
function which makes the supply air and exhaust air go through the heat recovery exchanger by pass
with energy saving control. "
1
© ISO 2022 – All rights reserved

---------------------- Page: 5 ----------------------
ISO/DIS 5222-1:2022(E)
3.3
coefficient of energy, sensible heating
COE
SEN_h
total sensible heating energy exchanged between the air streams plus the power value of moving air,
divided by the power input.
Note 1 to entry: The formula for determining the COE is given in clause 6.2.1 and 6.2.2.
SEN_h
3.4
Gross effectiveness, sensible heating
measured effectiveness, not adjusted for leakage, motor heat gain, or heat transfer through the unit
casing.
Note 1 to entry: The sensible heating gross effectiveness of an HRV, at equal airflow, is described in ISO 16494-1
9.5.
3.5
power value of moving air
rate of pressure energy and kinetic energy of the air delivered by the ventilator.
Note 1 to entry: The formula that determines the power value of moving air is given in ISO 16494 9.6.1.
3.6
net supply airflow
Q
SANet
portion of the leaving supply airflow that originated as entering supply airflow.
3
Note 1 to entry: The net supply airflow is expressed in m /s.
Note 2 to entry: The formulas for determining net supply air flow are given in ISO 16494-1 9.4.1(ducted units)
and 9.4.2 (un-ducted units)
3.7
rating points
sets of supply and return airflow, static pressures at inlets and outlets, and speed control setting,
achieved during the airflow performance measurement, at which thermal performance tests and
exhaust air transfer tests are performed.
3.8
sensible heating recovery rate
rate of sensible heat recovery from the exhaust air flow.
3.9
maximum rated airflow
the highest supply and return airflow, specified by the manufacturer, confirmed by the airflow
performance measurement.
Note 1 to entry: For ventilators with speed control devices, different maximum rated air flows may be defined for
each speed control setting at which the measurement is performed.
3.10
minimum rated airflow
the lowest supply and return airflows, specified by the manufacturer, confirmed by the airflow
performance measurement.
Note 1 to entry: For ventilators with speed control devices, different minimum rated airflows may be defined for
each speed control setting at which the measurement is performed.
3.11
speed control device
device integrated into the ventilator which controls the speed of the fan for changing the airflow rate
and power input.
2
  © ISO 2022 – All rights reserved

---------------------- Page: 6 ----------------------
ISO/DIS 5222-1:2022(E)
3.12
standard air
3
dry air with a density of 1,200 kg/m .
3.13
static pressure differential
absolute difference between inlet static pressure and outlet static pressure for each of the two air
streams.
EXAMPLE Static pressures measured at │X -X │, or │X -X │.
2 1 4 3
3.14
Bypass outdoor temperatureT
bypass
outdoor temperature in heating conditions, at which the electric power inputted to the HRV for
overcoming the airflow resistances of heat recovery core is equal to the sensible heat recovered by the
HRV.
3.15
Seasonal performance factor of sensible heating recovery
SPF
SEN_h
ratio of seasonal amount of sensible heat recovered together with power value of moving air to the
whole electricity input of HRV, under the rating conditions and annual outdoor temperature bins
selected from this standard.
3.16
Building heating balance temperature
T
BHB
the outdoor air temperature at which building internal heat gain and solar radiation etc , equals to heat
loss to outdoor.
4 Symbols and Abbreviated terms
Symbol Description Unit
C Capacity of seasonal sensible heating recovery Wh
SSEN_h
COE Energy coefficient of sensible heating recovery W/W
SEN_h
c Specific heat of air kJ/kg· °C
p
L (t ) Reference outdoor air sensible heating load at outdoor air bin tem- W
SEN_h j
perature t
j
n Bin hours which the outdoor air bin temperature occurs h
j
n, m Number of temperature bins -
P (t ) Input power to ventilator at outdoor air bin temperature t W
in j j
P (t ) Sensible heat recovery power input of the HRV at outdoor air bin W
SEN_h j
temperature t
j
P (t ) Ventilation power input of the HRV at outdoor air bin temperature t W
VENTILATION j j
P Power value of moving air J/s or W
vma
PI Electricity power input of seasonal sensible heating recovery Wh
SSEN_h
SPF Seasonal performance factor of sensible heating recovery Wh/Wh
SEN_h
T the outdoor air temperature at which building internal heat gain °C
BHB
equals to heat loss to outdoor
T Outdoor air temperature when HRV operates under air bypass function °C
bypass
T The outdoor air bin temperature at which the frost occurs °C
FROST
ΔP The air flow resistance of heat recovery exchanger combined with Pa
E-heat exchanger
the air channel of exhaust side
3
© ISO 2022 – All rights reserved

---------------------- Page: 7 ----------------------
ISO/DIS 5222-1:2022(E)
ΔP The air flow resistance of heat recovery exchanger combined with Pa
S-heat exchanger
the air channel of supply side
ε Gross sensible heating effectiveness of HRV %
SEN_h
η The efficiency of fan, assumes as 0,6 . -
fan
ϕ (t ) Sensible heat recovery capacity of the HRV at outdoor air bin tem- W
SEN_h j
perature t
j
5 Tests
5.1 General requirements
The tests conditions used, the accuracy and uncertainties of the instruments used shall conform with
the ISO 16494-1 and those in this standard.
5.2 Test conditions
For the purpose of ε , COE and SPF , there are three standard test conditions T5/T6/
SEN-h SEN_h SEN-h
T7 corresponding to ISO 16494-1 table 2, combined with three application temperature bin types
A(average) , W(warmer) and C(colder).
Temperature and humidity conditions as well as default values for test and calculation shall be as the
requirement specified in Table1.
Table 1 — Conditions of performance test (heating)
Outdoor air temperature Indoor air temperature Application temper-
(°C) (°C) ature bin type for
calculation
Dry bulb Wet bulb Dry bulb Wet bulb
T5 2 1 21 14 In Annex B or D
T6 5 3 20 15
T7 7 6 20 12
NOTE: Allowable variation of readings is given in tables F.2. in ISO 16494-1
5.3 Test methods
For higher seasonal energy performance, HRV can be designed with air flow bypass function integrating
fan speed control or airflow dumps adjust , which can change the fan power input according to different
outdoor temperature condition ,while keeping necessary aerodynamic performance.
5.3.1 energy saving stage limit temperature
For assessment the energy saving ability of HRV, the operation stages under the application temperature
bin are showed in Annex A using a schematic diagram.
5.3.2 sensible heating recovery performance test
5.3.2.1 Standard condition performance tests
The sensible heating recovery performance tests shall be conducted in accordance with ISO 16494-1.
The sensible heating recovery performance, efficiency as well as airflow and static pressure shall be
measured corresponding to the selected standard heating performance tests conditions as table 1.
4
  © ISO 2022 – All rights reserved

---------------------- Page: 8 ----------------------
ISO/DIS 5222-1:2022(E)
5.3.2.2 Determination of performance at application climate
The sensible heating recovery performance under certain climate temperature bins shall also be
determined in accordance with ISO 16494-1, by substituting of outdoor temperature using the climate
bins temperature see Annex B and D.1
5.3.3 The determination of bypass outdoor temperature
For the determination of bypass outdoor temperature, it should use ways as below:
a) The manufacture specifies the value of bypass outdoor temperature, but the lab shall verify
whether the tested unit is with the function and what is the action temperature by test in lab.
b) If the manufacture doesn’t specify it, calculating it out following annex E by referring to the
definition.
c) compare the value of a)and b), define the lower as the T .
bypass
5.3.4 Measurement of power input of heat recovery ventilator with bypass ventilation function.
5.3.4.1 Due to the additional air resistance of heat recovery exchanger, when the heat recovery
profit is less than the additional energy input due to overcoming the resistance of heat exchanger,
the equipment may provide with the bypass ventilation function to reduce the additional energy
consumption, when only ventilation is necessary.
5.3.4.2 When the bypass ventilation function acts, there may be several means to reduce the
additional energy consumption, for example with fan speed control or valve control in fan’s inlet or
outlet etc. to keep the same airflow rate and pressure as rating performance condition.
5.3.4.3 The manufacturer may provide information on how to set the bypass function if requested by
the testing laboratories.
5.3.4.4 The tests below shall be conducted at the required control setting which allows steady state
operation of the equipment at the given test conditions.
5.3.4.4.1 Test of unit with bypass ventilation function and fan speed control
a) Set up the bypass ventilation function according to manufactures’ instruction.
b) Adjust test auxiliary device to keep the average pressure value at air outlet and inlet of unit in
Figure A.1 of ISO 16494-1 within the 5% of tested unit’s nominal value, the air flow rate larger or
equal to its nominal value
c) According to the ISO 16494-1, measure and record the data of air flow rate, the pressure and
electricity power input
d) Determine and record the outdoor temperature at which the bypass ventilation function acts,
either by manufacturer's statement, or by measure. The power input value measured when bypass
ventilation functions is activated is recorded as the bypass ventilation function power input, used
for calculation for SPF corresponding to each outdoor bin temperature in ventilation period.
SEN_h
5.3.4.4.2 Test of unit with bypass ventilation function and with electric driving air damper
automatically, but without fan speed control.
a) Set up the bypass ventilation function according to manufacture instruction
b) Adjust test auxiliary device to keep the average pressure value within the 5% of tested unit’s
nominal value, the air flow rate larger or equal to its nominal value.
5
© ISO 2022 – All rights reserved

---------------------- Page: 9 ----------------------
ISO/DIS 5222-1:2022(E)
c) Determine and record the outdoor temperature at which the bypass ventilation function acts, either
by manufacturer's statement, or by measurement. The power input value measured when bypass
ventilation function is on shall be recorded as the bypass ventilation function power input, used for
calculation for SPF corresponding to each outdoor bin temperature in ventilation period.
SEN_h
5.3.4.4.3 Test of equipment with bypass ventilation function and without fan speed control and
without automatic adjust air damper
a) Set up the bypass ventilation function according to manufactures’ instruction
b) According to the ISO 16494-1, don’t adjust any of the test auxiliary devices during test and record
the data of air flow rate, the pressure and power input.
c) Determine and record the outdoor temperature that the bypass ventilation function acts, either by
manufacturer's statement, or by test.
d) The power input value measured when bypass ventilation functions on is recorded as the bypass
ventilation function power input, used for calculation for SPF corresponding to each outdoor
SEN_h
bin temperature in ventilation period.
5.3.4.4.4 Test of equipment with no bypass ventilation function
For the equipment with no bypass ventilation function, the power input is the value as same as in 5.3.2.1
all stages, which shall be used for calculation for SPF corresponding to each outdoor temperature in
ventilation period.
5.3.5 Determination of the frosting temperature by test
The frost occurring temperature tests shall conducted in accordance with ISO 16494-1.
The manufacturer may provide information on how to operate the equipment if requested by the
testing laboratories.
5.3.5.1 The test condition shall be as bellow:
a) The airflow rate and static pressure shall keep the same as 5.3.2.1.
b) The return air temperature shall be kept at conditions T5/T6/T7 specified in table 1 and outdoor
air temperature shall be gradually reduced from 0 °C, or, in order to reduce the duration of the test,
from the pre-T , which is described in annex C, plus 2K.
FROST
5.3.5.2 Confirmation of frost outdoor air temperature
a) Turn off the supplement heat function for anti-frost.
b) Conduct the tests of gross sensible heating recovery efficiency of HRV by changing outdoor
temperature from the pre- T plus 2K to more lower temperature. While adjusting the outdoor
FROST
air temperature, keep the reducing rate of temperature not less than 0,5K per hour and not greater
than 1,0K per hour.
c) Record the inlet and outlet air parameters so that gross sensible heating efficiency can be calculated
every 0,5h.
d) Calculate the gross sensible heat efficiency in accordance with clause 9.5 in ISO16494-1.
e) If absolute value of change rate of the gross sensible heating efficiency between the outdoor
temperature t and temperature t is greater than 5% , the higher temperature of the outdoor
j j-1
temperatures is confirmed as a frost outdoor temperature.
6
  © ISO 2022 – All rights reserved

---------------------- Page: 10 ----------------------
ISO/DIS 5222-1:2022(E)
f) compare the T tested and the one practical acts, if the T tested is lower than the one
FROST FROST
practical acts, select the temperature practical acts as the stage limitation temperature, otherwise,
the T tested shall be the stage limitation temperature.
FROST
5.3.5.3 Data collection
During the frost temperature tests, airflow rate, static pressure, barometer pressure and power input
as well as air temperature shall be collected and recorded. Continuously air temperature variation
curve drawing shall be necessary.
6 Calculations
6.1 Gross sensible heating recovery efficiency (ε )
SEN_h
The gross sensible heating recovery efficiency of HRV at rated test condition is described in ISO 16494-1
9.5.
6.2 Sensible heating coefficient of energy
6.2.1 Sensible heating coefficient of energy: ducted ventilators
The sensible heating coefficient of energy (COE ) for a ducted ventilator is described by the
SEN_h
following formula:
qc*** Tt− åP*1000+
()
mn20,_et pSj EN hvma
COE = (1)
SENh_ ducted
P ()
in
where
T is the dry temperature of entering exhaust airflow temperature (RA)to ISO 16494-1 standard
0
testing conditions(T5/T6/T7), (°C);
t is the dry temperature of outdoor air corresponding to application temperature bin j, (°C);
j
q is the net supply mass flow rate (kg/s);
m2,net
c is the specific heat of air(kJ/kg· °C);
p
ε is the gross sensible heating recovery efficiency of HRV at rated test condition is described
SEN_h
in ISO 16494-1-2014 8.5.
P is the power value of moving air (J/s);
vma
P (t ) is the input power to ventilator (W).
in j
6.2.2 Sensible heating coefficient of energy: unducted ventilators
The sensible heating coefficient of energy (COE ) for a unducted ventilator is described by the
SEN_h
following formula:
qc*** Tt− å *1000
()
mn20,_et pSj EN h
COE = (2)
SENh_ unducted
Pt
()
in j
7
© ISO 2022 – All rights reserved

---------------------- Page: 11 ----------------------
ISO/DIS 5222-1:2022(E)
where
T is the dry temperature of entering exhaust airflow temperature (RA)to ISO 16494 standard testing
0
conditions(T5/T6/T7) (°C);
t is the dry temperature of outdoor air corresponding to application temperature bin j (°C);
j
q is the net supply mass flow rate (kg/s);
m2,net
c is the specific heat of air(kJ/kg· °C);
p
ε is the gross sensible heating recovery efficiency of HRV at rated test condition is described in ISO
SEN_h
16494-2014 8.5.
P (t ) is the input power to ventilator (W).
in j
6.3 Calculation of seasonal performance factor of sensible heating recovery (SPF )
SEN_h
6.3.1 Reference outdoor air heating load and sensible heating recovery capacity
The reference outdoor air heating load shall be by a set of value and be assumed that they are linearly
changing depending on the change of outdoor temperature, the sensible heat recovery capacity is
assumed also linearly changing, see figure in annex A. Conditions of reference heating load and recovery
capacity is shown in Table 2.
Table 2 — Reference outdoor air sensible heating load and recovery capacity
T5 T6 T7
Outdoor air Temperature(°C) Climate bins Climate bins Climate bins
T Indoor air Tempera- 21 20 20
0
ture(°C)
Outdoor air heating load(W) L (t ) L (t ) L (t )
SEN_h,under T5 j SEN_h,under T6 j SEN_h,under T7 j
recovery capacity(W) ϕ (t ) ϕ (t ) ϕ (t )
SEN_h,under T5 j SEN_h,under T6 j SEN_h,under T7 j
where T is the temperature at which outdoor air heating load assumed zero.
0
Outdoor air sensible heating load L (t ) at outdoor temperature t , whi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.