This document specifies requirements for fire resisting data cabinets and diskette inserts.
Two methods of test are specified to determine the ability of fire resisting data cabinets to protect temperature and humidity sensitive contents from the effects of fire: a fire endurance test and a fire shock and impact test. Two levels of fire severity (S 60 and S 120) based upon time of fire exposure; and three protection classes (P, D and DIS) are specified using the maximum temperature increases and humidity values permitted within the storage space of the data cabinet.
Diskette inserts (DI 60 P/DIS and DI 120 P/DIS) are installed in data cabinets of protection class S 60 P or S 120 P, respectively, and subjected to a fire endurance test (see 5.1.2).
Requirements are also specified for test specimens, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures.
A scheme to classify the fire resisting data cabinets and diskette inserts from the test results is also given (see Table 1).
Diskette inserts are only installed in data cabinets having the same design as the series of protection class S 60 P and S 120 P, respectively, in which the insert has been tested in using methods defined in 5.1.2. Where several inserts are installed, they are built in one beside the other or one above the other from bottom to top, respectively. The volume and total height of the installed inserts do not exceed 50 % of the total internal volume or 50 % of the internal height, respectively, of the data cabinets into which they are installed. The dimensions of the insert can be adapted by increasing the width and depth to the corresponding dimensions of the data cabinets. A reduction of these dimensions as well as a change of the height is only admitted within the specified tolerance.
The temperature increases during type-tests on data cabinets and diskette inserts will be considered in deciding the permitted diskette insert installations. For a permitted installation, the temperature increase of the intended data cabinet ( ) does not exceed the temperature increase of the tested data cabinet ( ) in which the diskette insert has been type-tested by more than the difference between the maximum value for the diskette insert ( ) and the maximum admissible temperature increase (30 K), i.e   (See example in Annex B).
A description of the installation of the diskette inserts can be given in the technical documentation of the manufacturer.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies requirements for light fire storage units providing protection against fire.
The method of test is specified to determine the ability of light fire storage units to protect paper media from the effects of fire. Two levels of fire exposure periods (LFS 30 and LFS 60) are specified using the maximum temperature increase permitted within the storage space of the light fire storage unit.
Protection after the fire exposure of 30 min (LFS 30) or 60 min (LFS 60) is not ensured by this document, but by European Standard EN 1047-1. Requirements are also specified for the test specimen, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures.
A scheme to classify the light fire storage units from the test results is also given (see Table 1).

  • Standard
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of the European Standard EN 1047 specifies requirements for data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive data media (see 3.5) and hardware systems (see 3.6) from the effects of fire. A test method for measuring the resistance to mechanical stress (impact test) provided by data rooms type B and data containers is also specified.
Requirements are also specified for test specimens, the technical documentation of the test specimens, materials specimens, physical fittings, the correlation of test specimens with the technical documentation and the preparation for type testing, as test procedures as well as the series production.
In addition, a scheme to classify data rooms and data containers from the test results is given (see Table 1).
As well as providing protection against fire, correctly installed data rooms and data containers offer a defined protection against impacts caused by failure during fire of components and objects external to the data room or data container.
Data rooms and data containers having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, lockings, doors, etc.) will only be given the same protection classification as that of the test specimen if the tolerances are within the ranges specified in Clause 7.
NOTE   This European Standard does not regulate the use of data rooms in the meaning of the building laws of the respective countries. In the construction of data rooms, it is advised to consider the respective national requirements.

  • Standard
    35 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Data rooms and data containers are fire protection security products whose purpose is to protect temperature and humidity sensitive data media and hardware systems from the effects of fire. These fire resistance products do not provide any defined protection against burglary.
Based on these objectives, the CEN/TC 263 Working Group WG2 Fire Resistance unanimously noted at its meeting on 8 March 2012 that the requirement for a certified high security lock according to EN 1300 for data rooms and data containers suggests protection that is not provided and does not reflect the requirements of the market.
For the reasons explained above, WG2 unanimously recommended deletion of the requirements for a certified high security lock according to EN 1300 without replacement from EN 1047-2:2009. In the interest of the market, this change in this European Standard shall be implemented very soon via an Amendment to EN 1047-2:2009. The necessary decision shall be taken in a 3 months shortened UAP. The necessary application shall be filed with the CEN/TC 263 via DIN.
The draft for Amendment A1 to EN 1047-2:2009 shall be presented to the CEN/TC 263 together with the application for changes in this European Standard.

  • Draft
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of this European Standard specifies requirements for fire resisting data cabinets and diskette inserts.
Two methods of test are specified to determine the ability of fire resisting data cabinets to protect temperature and humidity sensitive contents from the effects of fire: a fire endurance test and a fire shock and impact test. Two levels of fire severity (S 60 and S 120) based upon time of fire exposure; and three protection classes (P, D and DIS) are specified using the maximum temperature increases and humidity values permitted within the storage space of the data cabinet.
Diskette inserts (DI 60 P/DIS and DI 120 P/DIS) are installed in data cabinets of protection class S 60 P or S 120 P, respectively, and subjected to a fire endurance test (see 5.1.2).
Requirements are also specified for test specimens, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures.
A scheme to classify the fire resisting data cabinets and diskette inserts from the test results is also given (see Table 1).
Cabinets having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, locking, etc.) will only give the same fire protection classification as that of a test specimen if they are of similar internal dimensions. The maximum difference in internal dimensions (height, width and depth of the storage space, measured from wall to wall) to which the test classification could apply is + 15 %. Cabinets having internal dimensions which differ by more than this amount from that of the tested specimen should be submitted to an extra test.
The wall, ceiling and door thicknesses should not be below the specified minimum limit of the type-tested thickness by more than 3 %. ...

  • Standard
    23 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies requirements for light fire storage units providing protection against fire.
The method of test is specified to determine the ability of light fire storage units to protect paper media from the effects of fire. Two levels of fire exposure periods (LFS 30 P and LFS 60 P) are specified using the maximum temperature increase permitted within the storage space of the light fire storage unit.
Requirements are also specified for the test specimen, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures.
A scheme to classify the light fire storage units from the test results is also given (see Table 1).

  • Standard
    13 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of the European Standard EN 1047 specifies requirements for data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive data media (see 3.5) and hardware systems (see 3.6) from the effects of fire. A test method for measuring the resistance to mechanical stress (impact test) provided by data rooms type B and data containers is also specified.
Requirements are also specified for test specimens, the technical documentation of the test specimens, materials specimens, physical fittings, the correlation of test specimens with the technical documentation and the preparation for type testing as well as test procedures.
In addition, a scheme to classify data rooms and data containers from the test results is given (see Table 2).
As well as providing protection against fire, correctly installed data rooms and data containers offer protection against impacts caused by failure during fire of components and objects external to the data room or data container.
Data rooms and data containers having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, lockings, doors, etc.) will only be given the same protection classification as that of the test specimen if the tolerances are within the ranges specified in Table 1.
NOTE   This European Standard does not regulate the use of data rooms in the meaning of the building laws of the respective countries. In the construction of data rooms, the respective national requirements should be considered.

  • Standard
    34 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Part of the European Standard EN 1047 specifies requirements for data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive data media (see 3.5) and hardware systems (see 3.6) from the effects of fire. A test method for measuring the resistance to mechanical stress (impact test) provided by data rooms type B and data containers is also specified.
Requirements are also specified for test specimens, the technical documentation of the test specimens, materials specimens, physical fittings, the correlation of test specimens with the technical documentation and the preparation for type testing as well as test procedures.
In addition, a scheme to classify data rooms and data containers from the test results is given (see Table 2).
As well as providing protection against fire, correctly installed data rooms and data containers offer protection against impacts caused by failure during fire of components and objects external to the data room or data container.
Data rooms and data containers having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, lockings, doors, etc.) will only be given the same protection classification as that of the test specimen if the tolerances are within the ranges specified in Table 1.
NOTE   This European Standard does not regulate the use of data rooms in the meaning of the building laws of the respective countries. In the construction of data rooms, the respective national requirements should be considered.

  • Standard
    34 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of EN 1047 specifies requirements for fire-resisting data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive contents and associated hardware systems from the effects of fire outside the data room or data container. A test method for measuring the resistance to impact of data containers and some data rooms is also specified.

  • Standard
    24 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of this European Standard specifies requirements for fire resisting data cabinets. Two methods of test are specified to determine the ability of fire resisting data cabinets to protect temperature and humidity sensitive contents from the effects of fire: a fire endurance test and a fire shock and impact test.

  • Standard – translation
    19 pages
    Slovenian language
    sale 10% off
    e-Library read for
    1 day